Abstract
A protective structure should be sufficiently resilient to protect its occupants from the harmful effects of an impact or explosion. In many instances, protective structures are also required to be assembled quickly, and be cost-effective. Steel-concrete-steel (SCS) sandwich structures combine the benefits of steel; ductility and anti-scabbing, and concrete; energy absorption and rigidity. Despite these favourable characteristics, the performance of profiled-plate steel-concrete-steel structures under blast and impact loads has yet to be studied in detail. This article presents the results from a numerical study investigating the efficacy of a newly proposed profiled-plate arched steel-concrete-steel structure under the loading from an extremely near-field high explosive detonation. It is observed that as arch thickness (concrete infill depth) increases, a greater proportion of energy is absorbed through concrete crushing and a larger concrete mass is mobilised. It is shown that a 240 mm arch thickness is adequate to resist the blast load from a 5.76 kg TNT charge, therefore proving the suitability of the proposed protective structure.
Introduction
Protective structures should be designed to shield their inhabitants from a range of malicious attacks. One such form of attack, which is the focus of this article, is the use of high explosive (HE) projectiles with the specific intention of causing partial or total collapse of the structure, or damaging the fabric of the structure in a way that compromises its protective ability. Protective structures are common in conflict zones worldwide, and the need for protective structures to be rapidly assembled is often paramount.
The Korean peninsula is a particularly active area of conflict between two neighbour states. In 2010, Yeonpyeong Island was the scene of an artillery engagement between the North Korean military and South Korean forces which resulted in the deaths of up to 15 people and over 50 casualties. In response to this, South Korea began to fortify military facilities and certain civilian shelters using corrugated steel plates as an efficient, cost-effective and lightweight alternative to reinforced concrete (RC). Numerical and experimental studies have shown the efficacy of earth-covered corrugated steel protective structures (Kim and Lee, 2015); however, to date, there has been no research into corrugated steel protective structures for deployment in situations where construction time is severely constrained.
This article presents the design of a new type of protective structure designed specifically for rapid construction: a corrugated steel-concrete-steel (SCS) sandwich structure. Numerical analysis is used to assess the performance of this newly proposed structure under blast loads and comments are made on the suitability of the proposed design.
Literature review
Many blast protection systems exist, each with varying levels of blast resistance and robustness, ease of construction and cost (Smith, 2010). This literature review aims to compile current structural blast protection techniques and evaluate them against these three criteria. The first criterion is commonly evaluated in the literature through numerical and experimental studies, as blast resistance generally has the greatest importance when considering the adequacy of a protective system. While ease of construction and cost are rarely discussed, they are no less significant for real-life systems.
Fibre-reinforced polymer (FRP) sheets have been used to retrofit existing structures to offer increased blast resistance and ductility. Razaqpur et al. (2007) experimentally tested bare RC panels and RC panels with glass fibre-reinforced polymer (GFRP) sheets adhesively bonded to the front and back faces. The panels were subjected to ANFO charges detonated at scaled distances of
Steel fibre-reinforced polymers (SFRPs) are more affordable than CFRPs and have been shown to increase the strength of FRP-wrapped RC columns to a similar extent (Berger et al., 2012), although FRP-wrapped beams are unlikely to demonstrate such an increase in strength owing to the propensity for tensile failure in blast-loaded RC beams (Carriere et al., 2009), as opposed to scabbing or shear failure associated with RC columns. Alternatively, polyurea or polyurethane sprays can be applied directly to a structure to enhance its blast performance (the reader is directed to Raman et al., 2011, for a detailed review). These retrofitting methods, while cost-effective and relatively simple to implement, are only suitable for preexisting structures and are not yet applicable for the design and build of new systems.
SCS sandwich structures combine the benefits of steel; ductility and anti-scabbing; and concrete; energy absorption and rigidity (Liew and Sohel, 2009). This construction technique permits high slenderness ratios as the steel layers act as framework during construction, and the concrete does not require additional reinforcement. Composite action can be achieved through shear connectors which prevent shear failure in the concrete and limit separation of the steel by effectively coupling the deflections of both top and bottom plates (Liew et al., 2017). In order to house these shear connectors, however, the SCS panels should be no less than 210 mm thick (Smith, 2010), whereas non-composite SCS panels as thin as 50 mm have demonstrated adequate blast resilience against near-field high-explosive blasts (Remennikov and Kong, 2012; Wang et al., 2015a). Arched SCS sandwich panels have been shown to displace considerably less than straight SCS panels under dynamic loads: as little as 13% of the residual displacement of straight panels (Liew et al., 2017), and have been suggested for use in diverse applications from blast walls to Arctic caissons to resist the impact load from ice floes (Wang et al., 2016).
Profiled-plate steel sandwich panels are a variation of SCS structures using steel plates formed into different shapes, for example, sinusoidal or trapezoidal, and are used in various applications owing to their increased resistance against different types of loading when compared to flat plates. To date, there have been few studies which have investigated the performance of profiled-plate SCS structures under blast and impact loads, as identified in the review of Hilo et al. (2015). Despite limited studies into the effectiveness of profiled-plate sandwich structures, there is some evidence to suggest that such systems have increased cracking resistance and buckling resistance due to confinement offered by the steel plates (Rafiei et al., 2017). In addition to this, a number of studies demonstrate the effectiveness of using bare profiled steel plates as blast walls, particularly in offshore structures (Boh et al., 2004; Kim et al., 2014; Malo and Ilstad, 1994).
Wang et al. (2016) showed that the provision of shear connectors between the steel plates could increase the performance of profiled-plate SCS structures. However, removing the need for shear connectors simplifies the construction and reduces the need for significant pre-fabrication and increased transportation costs. The stackable nature of profiled steel plates also lends itself to efficient transportation. As such, in this article, we neglect composite action and rely only on friction between the concrete and steel, as per Remennikov and Kong (2012), to provide a conservative design solution.
It is posited that un-composite, profiled-plate SCS structures offer a suitable compromise between the strength of a composite SCS structure and the practicality of a flat-plate SCS structure. An arched SCS sandwich structure using corrugated steel plates, therefore, offers the greatest potential for a rapid-construction protective structure.
Design of SCS protective structure
Design threat
In the military domain, protective structures are subjected to aggressive loads from a number of different sources. Impacts from artillery shells or munitions generate large amounts of kinetic energy and momentum within the structure; however, these events are generally considered less significant as protective structures possess sufficient mass to absorb the energy and prevent global deformation or failure. Reinforcing concrete structures with steel plates will significantly improve impact resistance: the hardness of the exterior plate (relative to concrete) will deform or fracture the projectile, reducing its capacity to penetrate the target, and the interior plate (also called the ‘backplate’) will prohibit scabbing or spalling of the back face of the concrete. Hence, a SCS panel can be expected to have a higher resilience against impact threats when compared to a single sheet of steel or a bare RC panel.
Explosions transfer momentum and energy to a target through either direct interaction of blast pressures with the structure (air burst), ground motion and soil impact (below ground explosion), or a combination of the two (surface or near-surface burst). In this study, explosion effects have been identified as the critical case, and therefore, the proposed SCS structure will be analysed against the effects from bare explosives only, that is, ground motions will be neglected.
HE projectiles are commonly used in conflicts at the North/South Korean border, and are the focus of this study. HE projectiles are typically loaded with ~15% explosives by mass, and are fitted with either impact, proximity, or timed fuses, or a combination of these. Delayed impact allows the projectile to penetrate some distance into the target before it detonates to increase damage; however, these projectiles are expected to deform significantly when impacting a dense, hard material such as steel, or impinging on a profiled surface. As such, penetration is less significant an issue for the proposed design.
In this study, a 152 mm calibre artillery shell with 5.76 kg TNT net explosive quantity was chosen as the design threat (Jeon, 2018). The explosive was simplified as an equivalent sphere of TNT (equal mass: 0.095 m radius assuming a density of 1630 kg/m3) and detonation was assumed to occur shortly after impact. In order to build some degree of conservatism into the model, the centre of mass of the equivalent spherical charge was assumed to be 150 mm from the tip of the shell, as in Figure 1, that is, the casing is expected to deform and penetrate some distance into the structure while the main explosive mass is expected to remain outside the structure. For simplicity, the effects of fragmentation of the explosive casing and the momentum of the shell itself have been neglected in this study.

Geometry of a 152 mm calibre artillery shell (MSM Group, 2018) and simplified geometry used in this study.
Structural design specification
Recent research into SCS sandwich structures subjected to extreme loads showed that an arch with a rise-to-span ratio
Dimensions of the M-934 vehicle and protective structure.

(a) Schematic view of the protective structure and (b) profile of corrugated steel plate.
In order to satisfy the requirements of The Republic of Korea Defense Military Facilities Criteria, Design and Construction Guide for Steel Protective Structures, DMFC 5-70-80 (ROK Ministry of Defense, 2012), standard-depth corrugated steel should posses a yield strength of ⩾245 MPa, an ultimate tensile stress of ⩾400 MPa, an elongation at failure of ⩾25% and an elastic modulus of ⩾205 GPa. S275 steel possesses suitable properties (275 MPa yield strength, 430 MPa ultimate tensile stress and 30% elongation at failure), and hence, in this study, the steel is assumed to be S275 with an elastic modulus of 205 GPa. Standard-depth corrugated steel plates, specified in ROK Ministry of Defence (2012), should have pitch, depth and curvature radius of 15, 50 and 28 mm, respectively (Figure 2(b)). As thickness can range from 3.65 to 7.1 mm, a thickness of 6.32 mm is selected for the plates. DMFC 5-70-80 also specifies the overlapping of plates and bolt connection details. While it is recommended that the structure is built in this way, for the purposes of the numerical modelling in this article, the plates have been assumed to act as a single, continuous entity. This is justified with reference to the modelling work of Kim and Lee (2015), Tang et al. (2015) and Ju and Oh (2016).
Since rapid construction is a requirement for the protective structure, it is expected that the structure will be required to be fully functional within 24 h of construction; hence, a high early strength Portland cement should be used for the concrete infill. According to the Korean Standard, Portland Cement (KATS), KS L-5201 (2016), high early strength Portland cement falls into Category 3, and it must have a compressive strength of 10 MPa or higher after 24 h. Furthermore, the concrete should possess a characteristic strength,
For simplicity, it has been assumed that RC footings provide adequate lateral and rotational restraint at the supports such that the SCS structure can be assumed to be perfectly clamped.
Numerical modelling setup
Geometric representation
Numerical models were simulated using the LS-DYNA explicit solver, LSDYNA V971 R8.10 (Hallquist, 2006). The corrugated steel plates were represented using Belytschko–Tsay elements with two through-thickness integration points and appropriate controls to prevent hourglassing. For the concrete infill, constant-stress solid elements were chosen to better model complex behaviour and material failure in mechanisms such as scabbing and spalling.
A comprehensive mesh sensitivity analysis was performed as part of a preliminary modelling study in Jeon (2018). While detailed results are omitted here for brevity, the models analysed in this article were designed in accordance with the following findings:
The corrugated plates were created using line elements, connecting three keypoints per flat part and three keypoints per curved part of the plate, to match the profile in Figure 2(b)). An individual line segment (pitch 150 mm), comprising these keypoints, was copied to cover the length of the structure and then extruded into the arch shape (note the coordinate axes in Figure 2)
The converged element size for the corrugated steel plates was found to be 0.06 m, and the converged element size for the concrete infill was found to be 0.04 m
The centreline of the structure, in the direction parallel to the span of the arch, was specified as a symmetry boundary (see Figure 3). The charge was assumed to load the protective structure at some point along this symmetry line, with the exact impact locations to be defined later in this article
Preliminary findings indicated that it was not necessary to model the full length of the structure (where ‘length’ refers to the distance perpendicular to the span, as per Figure 3). Deformation histories for a 3.6 m structural length (1.8 m in half-symmetry) were found to closely match deformation histories for a full-length 9.6 m structure (4.8 m in half-symmetry). This is justified by the highly localised nature of the imparted loading and resultant structural deformation. The end of the structure remote from the symmetry plane was modelled as a free boundary as negligible deformations were expected

Geometry and dimensions of the numerical model.
Material properties
The steel was represented as a bilinear elastic-plastic material using the *
where
The concrete was modelled using the ‘continuous surface cap model’, *
*
Loading, boundary conditions and contact
Loading was applied to the structure using the *
where
Recent numerical (Shin et al., 2015) and experimental work (Rigby et al., 2015b) has shown that the Kingery and Bulmash (1984) predictions, particularly for reflected specific impulse, remain reasonably accurate at distances extremely close to an explosive charge. Applying the load directly to the structure removes the need to model a fluid domain surrounding the structure and associated, computationally expensive, fluid–structure interaction.
The structure was modelled using half-symmetry by assigning appropriate boundary conditions (constrained
Coupling between the steel plates and concrete infill was achieved using the *
Situations studied
Five different models were run. First, a 120-mm thick arch was analysed under three different blast loads: (1) a 5.76 kg spherical TNT charge, detonated as a free air burst at 150 mm stand-off (to-centre) directly above the top-centre of the arch; (2) a 5.76 kg spherical TNT charge, detonated as a free air burst at 150 mm stand-off (to-centre), half-way between the ground surface and the top of the arch; and (3) a 5.76 kg hemispherical TNT charge detonated on the surface, 150 mm stand-off (to-centre) from the base of the arch. These are labelled ‘Near-fields 1–3’ in Figure 4, and

Loading arrangements studied in this article.
An additional verification case was studied: that of a 5.76 kg hemispherical TNT charge detonated on the surface, 1800 mm stand-off (to-centre) from the base of the arch (‘Far-field’ in Figure 4); however, the results are omitted in this article as the structure remained elastic throughout and displacements were negligible. Once the worst-case loading scenario was identified from ‘Near-fields 1–3’ for the 120 mm arch thickness, two further models were run with this loading condition applied to 180 mm and 240 mm arch thicknesses. The steel plate thickness was kept constant at 6.32 mm throughout.
Figure 5 shows the magnitude and distribution of reflected pressure distributions on the roof of the protective structure (in plan view) at various instants in time. Here, the bottom edge of the structure acts as the symmetry boundary, and hence, the loading is symmetric above and below this line (as per the dashed line in Figure 5(a)). It should be noted that while the fringe levels are clipped at a reflected pressure of 100 MPa, the peak reflected pressure directly beneath the charge reaches a value of ~400 MPa. However, this pressure is highly localised and decays rapidly with both space and time. It can be seen that areas of the corrugated plate orientated towards the charge are subjected to a higher load, and those orientated away from the charge are subjected to a lower load owing to angle of incidence effects.

Pressure contours acting on the roof of the protective structure for ‘Near-field 1’ loading condition: (a) t = 0.05 ms, (b) t = 0.10 ms, (c) t = 0.15 ms, (d) t = 0.30 ms, (e) t = 0.50 ms and (f) t = 1.00 ms.
Assessment of SCS protective structure
Identification of worst-case loading scenario
The initial models were run for 30 ms under all three loading conditions, with the displacement-time history of the node located directly beneath the charge shown in Figure 6(a). In addition, the separation distance between the steel backplate and the concrete infill was calculated and is plotted in Figure 6(b).

Numerical results from worst-case loading study: (a) maximum resultant displacement in the steel backplate and (b) separation distance between concrete infill and steel backplate.
While the charge in ‘Near-field 3’ experiences an amplification from the ground surface, 1 the resultant displacement is still considerably less than the displacements under Near-fields 1 and 2. Provided the structure’s foundations are adequate to provide lateral and rotational restraint, the structure possesses sufficient shear resistance to resist this load.
Both the peak displacement and maximum backplate-concrete separation distance are greatest for Near-field 2. It is suggested that the (primarily) vertical loading imparted from Near-field 1 allows the structure to better contain the compressive thrust due to its arched shape, whereas in Near-field 2, a significant amount of lateral load is imparted, which results in greater displacement and separation.
Figure 7 shows fringe plots of resultant displacement of the steel backplate and effective plastic strain in the concrete infill, for Near-fields 1–3 load cases. The deformation in the steel plate is highly localised and the deformation and concrete damage at the edge of the structure remote from the charge is effectively zero, justifying the assumption that a structural length of 3.6 m is adequate to describe the response of the entire structure. Despite the high-magnitude loading, the steel does not reach its failure strain, and therefore, in all cases the interior of the structure is not breached. In Near-fields 1 and 2, there is a region of pulverised concrete close to the location of the charge, which is retained by the steel backplate. The percentage of concrete that has failed, by volume, is 7.8% and 7.4% in Near-fields 1 and 2, respectively. On account of the larger structural displacements and similar concrete failure, Near-field 2 is selected as the worst-case loading scenario.

Fringe plots of (a, c, e) maximum resultant displacement in the steel backplate and (b, d, f) effective plastic strain in the concrete for Near-fields 1–3 load cases, 120 mm arch thickness.
Effect of arch thickness
Two additional arch thicknesses were analysed under the Near-field 2 loading arrangement, 180 and 240 mm, and are compared against the results for the 120 mm thick arch. Analyses were run for 90 ms to allow for a more complete description of structural response. Figure 8(a) shows displacement-time histories of the nodes located directly beneath the charge for each arch thickness, and Figure 8(b) shows the separation distance between the steel backplate and the concrete infill for each arch thickness.

Numerical results from arch thickness study: (a) maximum resultant displacement in the steel backplate and (b) separation distance between concrete infill and steel backplate.
As expected, an increase in concrete infill results in a significant increase in stiffness and therefore a decrease in peak displacement. The maximum values of displacement are 192, 80 and 52 mm for the 120, 180 and 240 mm thick arches, respectively. It is interesting to note that, while a thicker arch demonstrates a stiffer response to the imparted blast load, there is not as pronounced a benefit on backplate-concrete separation distance (Figure 8(b)). The maximum separation distances are 64, 16 and 13 mm for the 120, 180 and 240 mm thick arches, respectively. Interestingly, the residual separation distance for the 240 mm arch is 11 mm, which is greater than the residual separation distance of 9 mm for the 180 mm arch.
The deformed profiles of the 180 mm thick and 240 mm thick arches differ from the profile of the 120 mm thick arch, as can be seen in the fringe plots of resultant displacement of the steel backplate and effective plastic strain in the concrete infill in Figure 9. As thickness increases, deformation in the steel backplate becomes lower in magnitude but is spread over a larger area. The concrete failure is also less localised, as more of the concrete mass is mobilised to resist the imparted load. In all, 7.2% of the concrete infill in the 180 mm arch fails (1680 kg, by mass), whereas 7.7% of the concrete in the 240 mm arch fails (2320 kg, by mass).

Fringe plots of (a, c, e) maximum resultant displacement in the steel backplate and (b, d, f) effective plastic strain in the concrete for 120–240 m arch thickness, Near-field 2 loading.
Table 2 shows the energy absorbed in each part for the different arch thicknesses studied. This confirms the observations that as arch thickness increases, a greater proportion of concrete is mobilised, and the work done by the steel backplate begins to increase with increasing thickness (beyond a certain value between 180 and 240 mm). This also explains why an increase in residual backplate-concrete separation was seen for the 240 mm thick arch (Figure 8(b)). The energy absorbed in the concrete layer is approaching the value of 50% as observed in Wang et al. (2016).
Energy absorbed in each part for different arch thicknesses.
There appears to be a trade-off between increased stiffness of a thicker arch and the corresponding increase in the mass of mobilised concrete and therefore greater requirements for the steel backplate to resist the inertia of the concrete as it spalls. While both 180 and 240 mm arch thicknesses appear to offer a suitable balance of these properties, it is suggested that (1) thicknesses below 180 mm do not possess sufficient stiffness and (2) there may be a critical thickness above 240 mm where the inertia of the failed concrete cannot be resisted by the steel backplate, and therefore, the structure is breached. The optimal arch thickness is therefore within the range of 180–240 mm.
Recommendations
DMFC 5-70-80 (ROK Ministry of Defense, 2012) provides limits on the allowable ductility ratio (peak displacement divided by elastic deflection limit) of a protective structure, namely, this value is not allowed to exceed 1.75 if tensile membrane action is prohibited, or 6.00 if tensile membrane action is allowed. These ratios were found to be approximately equal to displacements of 16.0 and 54.0 mm, respectively, for the structures analysed in this article. It was found that there was little sensitivity on this value for the different thicknesses of concrete infill, as the failure was primarily driven by deformation of the steel backplate which was the same thickness throughout.
Of the three arches studied, only the 240 mm thick arch meets this criteria (peak displacement of
Although none of the structures failed by breaching, both the 120 and 180 mm thick arches do not meet the criteria set in DMFC 5-70-80 (peak displacements of 192 and 80 mm, respectively) and do not offer adequate protection under the design threat. It was found, however, that all structures provided adequate resistance against the ‘Far-field’ loading condition (Figure 4), and therefore, a structure of 120 mm arch thickness provides adequate resistance against an indirect hit from the design threat.
Summary and conclusions
A review of the available literature identified a lack of studies investigating the performance of profiled-plate SCS protective structures. Such structures have the potential to be robust, simple to construct and cost-effective. This article presents the results from a numerical study on the efficacy of profiled-plate arched SCS sandwich structures using LS-DYNA (Hallquist, 2006). The structure is designed to house a M-934 military heavy truck, and has an internal width of 9.375 m, height of 3.750 m and length of 9.600 m. Steel and concrete properties and fabrication techniques are assumed to be in accordance with design guidance. Three different arch thicknesses are studied: 120, 180 and 240 mm. In all, 6.32 mm thick corrugated steel plates were used throughout.
A design threat is specified, namely, a 152 mm calibre artillery shell (5.76 kg TNT NEQ) detonated shortly after contact with the structure. The charge is modelled as an equivalent mass sphere with its centre located 150 mm from the surface of the protective structure. Loading is applied to the structure using the in-built *
It was observed that a considerable amount of concrete was pulverised by the blast load in the area close to the charge, but scabbing/spalling of the concrete was succesfully contained by the steel backplate for all structures analysed. The amount of failed concrete was seen to increase with increasing arch thickness as a greater proportion of the total energy was absorbed through concrete crushing. Accordingly, residual detachment between the concrete and steel backplate was also seen to increase when the arch thickness increased from 180 to 240 mm.
Of the structures studied in this article, it is concluded that a 240 mm arch, fabricated to standards specified in DMFC 5-70-80 (ROK Ministry of Defense, 2012) to allow for tensile membrane action in the steel backplate, provides adequate resistance against the design threat. This article therefore demonstrates the suitability of an arched SCS sandwich structure using profiled steel plate as a rapid-construction protective structure, which demonstrates favourable characteristics, namely, spalling/scabbing resistance, increased cracking and buckling resistance, and hardness/ductility from the profiled steel plates. The proposed structure is easier to assemble and more cost-effective than equivalent earth-covered structures currently in use.