Abstract
In this paper, the magnetic losses of a supply current sensor dedicated to circuit breakers are investigated. Measurements were performed using an accurate calorimeter covering a measurement range of [1 mW; 10 W]. Several frequencies and voltages were tested. A model of the sensor’s core material (NO SiFe sheet M250-50A) was built with the Loss Surface (LS) dynamic hysteresis model and implemented in a 3D FEM computation tool. The sensor was simulated and iron losses were computed. Comparison between experiments and simulation shows a high concordance that leads to conclude about the reliability of the LS model.
Keywords
Introduction
The continuous improvement of Schneider Electric’s sensors requires a good knowledge of the device behaviour and a constant evolution of the design approach developed. This study focuses on the magnetic losses analysis and prediction in the power supply sensors installed in the Masterpact® circuit breakers. Simulations using 3D FEM tools are commonly used for the design of this sensor, but they require compatible materials models. In this study, the LS (Loss Surface) hysteresis model is integrated in the FLUX software and used in the post processing mode for the losses computation. To verify the relevance of this approach, a comparison with experiment on a real device is necessary. As the sensor geometry is complex, conventional electric measurements are not valid and a calorimetric method is performed.
The masterpact® NW current sensor
Masterpact® circuit breakers are dedicated to low voltage high current distribution. The opening of these breakers relies on an electronic device allowing a large adaptability on current level rating and protection threshold. It gives also the possibility to integrate complex algorithms for the signal processing. This electronic device is designated by “Micrologic”. For obvious security reasons the Micrologic needs to be supplied from the same network that the breaker secures. Knowing that the Micrologic can’t stand power levels as high as those of the network it’s compulsory to regulate the power levels fed to the Micrologic. This is ensured by the Masterpact® NW power supply current sensor [1] (Fig. 1) associated to a suitable power supply circuit (Fig. 2). The magnetic circuit of the Masterpact® sensor is manufactured using non-oriented silicon iron sheets M250-50A. It supplies the circuit through its secondary coil. This power supply sensor is associated to a Rogowski coil for the current measurements.
In case of an incident, the energy stored in the capacitor is released to insure the opening of the breaker. These current breakers are designed to operate from 80 A to 2000 A. Our study focuses on the sensor installed in high amperage breakers.
For our study we identify five main parts of the sensor (Fig. 1): (a) secondary coil branch, (b) flank, (c) flank shunt, (d) shunt and (e) ring. There is a functional 2 mm air gap between the shunt (d) and the flank (b). The shunt allows a part of the principal magnetic flux to be deviated at high current levels in order to limit the secondary current level in an acceptable range for the Micrologic.

Masterpact® NW current sensor.

Power supply circuit.
The magnetic circuit is made from SiFe sheets punched in one piece, then stacked and assembled. Note that the angle between the induction and the lamination direction is variable (Fig. 3) conditioning the permeability and the reluctance of each area in the sensor. Otherwise, it’s clear that the sensor parts have various widths, thus the residual stress impact on the magnetic properties is also different [2]. These characteristics lead to an inhomogeneous distribution of the induction and so the iron losses. The result is a various shape of the induction signal B (t) depending on the sensor area (Fig. 4). Then we can highlight that the SiFe sheets are interlocked (Fig. 1) and the secondary coil is added after the sheets assembly which causes a residual air gap. These manufacturing methods generate a bridge joining the SiFe sheets [3] that induces a circulation of eddy current among the whole sensor thickness which leads to important dynamic losses.

Magnetic flux direction vs lamination direction in the sensor.

Induction B (t) at Ip = Ip max depending on sensor areas (simulated with secondary coil on short-circuit).
The modelling of the sensor using FLUX 3D, is realised assuming some simplifications on physical and design levels: isotropic material characterized by an average law B (H) measured on rolling and transverse directions of the sheet, no interlocks, no welding and no punching effects consideration. Otherwise, the secondary coil is short-circuited since the study focuses on high currents. Despite these simplifications, the simulations show consistent results in which we can observe the local induction (Fig. 5.a) and losses. These local losses result in a local overheating observed thanks to an IR thermography (Fig. 5.b).

Concordance between local induction (a) (simulations) and local overheat (b) (experiments) at Ip (2 kA-400 Hz).
All these characteristics highlight the complexity of the sensor behaviour and the difficulties of its iron losses prediction. That is why calorimetric experimentations are investigated to estimate the reliability of simulations.
Calorimetric bench
Developed at G2Elab, the calorimeter [4,5] used in this experiment is primarily devoted to characterize power electronic components up to 3 kV and 1 MHz and within the temperature range of −50 to +150 ° C. It is based on radiation energy transfer and uses a suitable vacuum enclosure (Fig. 6) which contains the heater and all temperature sensors. In order to insure a stable temperature reference the measurements cell is linked to a liquid Nitrogen container representing a heat well. The bridge is a bar made of a material chosen according to the measured temperature range. Moreover, given that a perfect isolation is impossible, a differential measurement method is adopted (Fig. 7). The cell is maintained at a fixed temperature T 0 without supplying the sensor (No load operation). The power needed for this task is P 0. Then we supply the sensor while maintaining the cell at the same temperature T 0. The sensor losses P s are added to the balance so that the calorimeter supply is reduced to P 1 < P 0 where P s = P 0 − P 1. In these conditions the calorimeter offers a measurement range from 1 mW to 10 W with an accuracy of 2% at 100 mW.

The calorimeter design.

Differential measurement method.
Measurements and power supply instruments for the sensor are outside the enclosure. In order to insure thermal isolation, vacuum stability and good electrical connections, technical conditions on electrical cables and connectors are very strict. As a result, the material used to insure all these conditions limits the current supply to 1 A.
The calorimeter, was designed for small electrical components and has never been used for a complex device as the sensor Masterpact® NW. So it doesn’t present the optimal condition for our application. Indeed, the current limit to 1 A is significantly lower than sensor practical operating current. As a solution, we decided to supply the sensor from its secondary coil (Fig. 8). The voltage across the secondary coil is linked to the main flux in the sensor by the Eq. (1). As I
mag
is low in the case studied, we could link induction with voltage and frequency.
We decided to control the sensor power supply voltage because of the particular configuration in the calorimeter. We injected various sinusoidal voltages: 10, 20, 30 and 40 V at various frequencies: 50, 100, 150, 200, 300 and 400 Hz. Then we measured the corresponding losses. The sensor losses P
s
are the sum of the iron losses P
Fe
and the copper Joule losses P
Cu
. Yet the coil and supply characteristics are known so are the Joule losses. Then we can deduce the iron losses (Eq. (2)). Except for the test 50 Hz 40 V, the copper losses are negligible so the measured sensor losses are mostly the iron losses contribution. Errors on P
Cu
measures are barely noticed (ϵCu2%).

Power supply of the sensor in the calorimeter.
Also the establishment of the secondary vacuum in the chamber needs time. Finally, the refill of the nitrogen container influences the energy balance inside the calorimeter and induces longer stabilization time for the measure in progress.
LS model
Several magnetic loss or magnetic hysteresis models exist in literature [6,7]. In this study we focused on LS model developed at G2Elab and implemented in the software FLUX (Altair - France). This model [8,9] is a scalar model of global hysteresis including both static and dynamic behaviour. It links the magnetic field H to the induction B and its derivative dB∕dt. In FLUX the LS model is applied as post-possessing. In these conditions we neglect the influence of the losses and hysteresis on the modelled system. The simulation is realized with FEM based on a bijective H (B) curve. The losses are estimated afterwards, after the reconstruction of the hysteresis cycle by calculating H for each couple (B, dB∕dt) obtained in each element.

Dynamic surface of LS model H dyn = f (B, dB∕dt).
In the LS model the magnetic field H is split into two contributions: static and dynamic identifiable independently (Eq. (3)). The static field is likewise split into two parts: the anhysteretic component H
anh
and the irreversible one H
irr
(Eq. (4)). The latter depends on the material history. The dynamic field is expressed by a polynomial formula (Eq. (5)) which parameters are obtained during the identification of the model. This interpolation gives the specific surface of the LS model (Fig. 9).
The LS static model parameters are identified using quasi-static cycles considering in our case a frequency of 10 Hz: a major cycle measured at the highest induction permitted by the experimental bench called B sat and few minor centered cycles obtained at lower inductions. The H anh (B) is obtained from the major cycle by averaging the field of the rising branch and the decreasing branch. The H irr (B) is built using reversal curves obtained by the model parameters.
The LS dynamic model parameters are identified using a set of about 20 hysteretic loops at the same induction B sat as the major cycle but at different frequencies, e.g. from 10 Hz to 2 kHz. The parameters 𝛼 nm are obtained by interpolating experimental data in order to fit the Eq. (3).
After the parameters identification, the magnetic field is reconstructed via Eq. (1). Verifications were performed as shown in Fig. 10 in order to evaluate the consistence of the model before implementation in FEM simulation tool.

Example of LS model verification: M250-50A, Sine 50 Hz.
To reproduce the calorimeter experiments, the LS model of the M250-50A material was implemented in FLUX 3D software and simulations have been performed in the same conditions as measurements. Figure 11 shows an example of induction distribution and highlights that the levels are lower than normal operation.

Induction levels at 40 V/50 Hz (secondary coil supply).
As previously mentioned, the main studied parameters are voltage and frequency. Both simulations and measures have been based on these parameters. In the measured power range and with a temperature T 0 = 30 °C the highest error on measured power is 1.5%. Our goal is the comparison between LS (simulated) losses and measured losses.
Iron losses versus voltage at a same frequency
Induction levels are lower than 1.2 T which indicates that induction signals in the sensor are still sine waves forasmuch the magnetic behavior is still linear for these levels. Some frequency values have been changed to 50.5 Hz in order to avoid instrumental resonance with the electrical network.
Except for the 40 V/50 Hz case, coil losses are effectively weak. The curves in Fig. 12 show a high concordance between measured losses and LS model results.

Calorimetric results vs LS simulations on iron losses of the Masterpact® NW at 50 Hz.
Comparison at same frequency for different voltages Masterpact® NW (Measures VS LS)
In this case more results are available so that the analysis is more precise and developed (Table 2). The same observations as for Table 1 can be done.
Comparison at same voltage for different frequencies Masterpact® NW (Measures vs LS)
Comparison at same voltage for different frequencies Masterpact® NW (Measures vs LS)
Working at a constant voltage and an increasing frequency leads to the decrease of the induction level and explains why the iron losses decrease (Fig. 12). However, this observation is true for f ≤ 300 Hz. Indeed, iron losses start to increase when the frequency becomes higher than 300 Hz as the cycle surface increases (Fig. 13). This result is explained by a more important contribution of eddy current in the dynamic losses at high frequency.
In this comparison, the consistence of simulated and measured losses behavior is more obvious as slope variations are in concordance (Fig. 14).

LS hysteretic loops of the Masterpact® NW at 40 V depending on frequencies.

Calorimetric results VS LS simulations on iron losses of the Masterpact® NW at same voltage.
This work highlighted many conclusions about the calorimeter, the sensors behaviour, the consistence of the LS model as well as the simulations and measurements of the Masterpact® NW.
The LS model shows satisfactory results. It describes accurately the Masterpact® NW behaviour with acceptable errors on most cases. This justifies all the energy and time devoted to the development of the LS model. In addition, this study was a first validation of the M250-50A LS model on real case. It also shows the weaknesses of the model at low inductions (B ≤ 0.3 T) and low frequencies (f ≤ 50 Hz). We are currently working on improving the accuracy and reliability of the LS model.
This work permitted the iron losses estimations on the Masterpact® NW in a different configuration from its devoted one. It was a relevant experimentation so a new calorimeter more suitable to test the Masterpact® NW sensor in real functioning conditions was designed and is under tests. The preliminary results are promising.
Finally, it was an interesting test of the calorimeter out of its normal use which highlighted its capabilities.