Abstract
A square concrete-filled double steel tubular (CFDST) column composed of a circular core concrete-filled tube offers the advantages of both square and circular concrete-filled steel tubular (CFST) columns. However, limited tests were performed to investigate the axial performance of CFDST slender columns. This paper investigates the behavior and design of square CFDST slender columns subjected to concentric loading. A total of eight columns, including six CFDST slender columns and two CFDST short columns were tested under concentric loading. The test parameter includes the slenderness ratio of the columns and the thickness of the inner tube. The ultimate load, failure modes and axial load-deflection relationships of CFDST slender columns are presented. It was observed that square CFDST slender columns failed due to the overall buckling of the columns together with the localized buckling of the steel tube and concrete crushing. Increasing the slenderness ratio and decreasing the thickness of the inner steel tube reduced the ultimate load of CFDST slender columns. The applicability of the existing design code of CFST columns in designing CFDST slender columns was evaluated. It was found that the existing design codes significantly underestimated the ultimate loads of CFDST columns.
Introduction
Concrete-filled steel tubular (CFST) columns are often used in constructing tall buildings and bridge piers to carry large axial loads. The steel tube confines the infilled concrete effectively and acts as formwork during the construction. The CFST columns offer better mechanical performance in terms of strength, ductility, seismic and fire performance compared to the traditional reinforced concrete columns (Ahmed and Liang, 2021; Ahmed et al., 2022; Ci et al., 2021a; Ci et al., 2021b). Existing studies showed that confinement was more uniform for the circular cross-section than the square or rectangular cross-sections of CFST columns; therefore, the strength and ductility of square or rectangular CFST columns are lower than their circular counterparts (Sakino et al., 2004). However, the square and rectangular cross-sections of CFST columns offer ease of connection to the beams; thus, are deemed a preferred cross-section for construction (Wang et al., 2017).
The concrete-filled double steel tubular (CFDST) columns, an improved version (cross-section) of CFST columns, can be constructed by placing two steel tubes concentrically and filling the sandwiched and core section with concrete. The inner steel confined core concrete significantly improves the mechanical performance of the CFDST columns in terms of strength, ductility, seismic and fire performance, providing better performance than the conventional CFST columns and concrete-filled double-skin steel tubular (CFDST) columns with inner hollow section (Ahmed et al., 2019c; Ci et al., 2021a; Ci et al., 2021c; Xiong et al., 2017). As illustrated in Figure 1(a), square CFDST column composed of a circular core concrete-filled tube offers the advantages of both square and circular CFST columns. Pei (2005); Qian et al. (2011); Qian et al. (2015); Wang et al. (2017) and Ahmed et al. (2019a) reported test results of CFDST short columns under concentric and eccentric loading. Test results showed that the inner tube improved the strength and ductility of CFDST columns. Numerical models were also developed for short CFDST columns with square cross-sections to investigate their behavior under axial loading (Ahmed et al., 2018; Ci et al., 2020; Wang et al., 2017). However, all the existing studies were focused on short CFDST columns with a maximum length-to-width ratio (L/B
0
) of 4. Generally, for investigating short CFDST columns, the length of the tested columns is limited to a maximum of 4 times the width of the square hollow section (SHS) to avoid the influences of the global buckling failure mechanism. A square CFDST column can be considered as a slender column if the L/B
0
ratio is greater than 4. However, until today, experimental investigation on square CFDST slender columns has rarely been performed. The only test found, based on an extensive literature review, was on three square CFDST slender columns performed by Liew et al. (2016), where the concrete strength of the columns was about 180 MPa. Test results showed that for very slender columns, the effective utilization of ultra-high-strength concrete was very minimum as the main failure of the columns was due to global buckling. On the contrary to square cross-section, more tests on circular CFDST slender columns were reported in the literature (Ibañez et al., 2017; Liew et al., 2016; Romero et al., 2017). In the absence of test data, Ahmed et al. (2019b, 2020) developed mathematical models to study the behavior of square CFDST slender columns under eccentric loading, considering preload effects, and developed design models. Cross-section of a square CFDST column composed of a circular core concrete-filled tube.
This study presents an experimental work performed on square CFDST slender columns under concentric loading. The test parameters included the slenderness ratio of the columns and the wall thickness of the inner tube. The accuracy of the existing design formulae of CFST columns specified by various design codes was also evaluated for the design of CFDST slender columns.
Test program
Preparation of test columns
A total of eight CFDST columns were tested in this study under concentric loading. The cross-section of the outer square tube was 200 × 200 mm and the diameter of the circular tube was 114 mm. While the thickness of the square tube was kept constant as 4.5 mm, two different wall thicknesses for the circular tubes, namely: 2.5 and 3.5 mm, were investigated. The tested columns were divided into two different groups (G1 and G2) according to the wall thickness of the circular tubes. The length of the columns (L) was changed to vary the slenderness ratio of the columns. Group G1 consisted of five columns, with the length-to-width ratio (L/
Details of square CFDST tested slender columns.
Note:
Properties of steel and concrete
Three different steel tubes including outer tube and inner tubes with different thicknesses were used to construct the CFDST columns. Standard tensile test coupons were performed according to GB/T 228.1-2010 (2010) to measure the steel properties. The stress-strain curves obtained from the tensile coupons test, presented in Figure 2, show an obvious yield plateau. Table 2 summarizes the steel properties obtained from the coupon tests. The yield strength Experimental stress-strain curves of steel tubes. Summary of the tensile coupon tests results. Note: ± represents the standard deviation of three coupon test results.
All columns were filled with ready mixed concrete having the same compressive strength. Three concrete cubes of 150 mm × 150 mm × 150 mm were cast and tested after 28 days to measure the compressive strength. The average compressive strength of the concrete cube was 47 MPa.
Instrumentation
All columns were tested using a 4000 kN hydraulic testing machine at the Beijing University of Technology, China. Considering the safety of the test and the height of the longest test specimen exceeding the height of the reaction frame, all test columns were loaded horizontally, as shown in Figure 3. In order to eliminate elephant foot buckling failure mode, both ends of all columns were restrained by steel clamps. The details of the steel clamps used in the tests are shown in Figure 4. The load was applied through two sets of loading devices, as shown in Figure 5, specially designed comprising loading and adapter plates. Similar loading devices were also used by Hadi and Widiarsa (2012) for testing composite columns. The loading plate had a unidirectional spherical hinge, as illustrated in Figure 6. The thickness of each adapter plate was 50 mm. Therefore, the distance from the hinge support to the other hinge support should be calculated as the sum of the length of the test specimens 100 mm. The end faces of the tested columns were coated with superhard gypsum and flattened to ensure evenness and to eliminate the gap between the columns and the loading adaptor plate. Test setup of a CFDST slender column under axial loading. Photo and schematic diagram of the fixed clamp: (a) steel clamps and (b) dimensions. Details of loading end of the test specimen. Photo and schematic diagram of the plate used for loading purposes: (a) loading plate and (b) dimensions of the loading plate.



The strain distributions of the tested columns were measured at the midheight of the columns using bi-directional strain gauges attached to the outer tube. Each bi-directional strain gauge included a pair of strain gauges to measure both the axial and hoop strains. Two pairs of bi-directional strain gauges were pasted on the tensile (H1-Z1) and compression (H3-Z3) sides of the midheight of the columns. The position of the bi-directional strain gauges is shown in Figure 7. The lateral and axial displacements of the tested columns were measured using displacement sensors. Except for Columns S-1-12 and S-2-12, lateral displacements of all tested columns were measured using three displacement sensors, whereas, for Columns S-1-12 and S-2-12, lateral displacements were measured using five sensors. The axial displacements of all tested columns were also measured during the tests using two displacement sensors. The arrangement of the test setup, including the placement of sensors and strain gauges, is shown in Figure 3. Before formal loading, each test column was preloaded to 100 kN. This was to remove any gap between the test columns and the loading devices. The columns were tested under displacement control at the rate of 1 mm/min. The end of the test was called when the axial deformation of the tested columns reached 30 mm. The DH18 acquisition system was used to record the data of applied load, strain gauges and displacement sensors. Position of the strain gauges on the square tube.
Test results
Failure modes
Figure 8 illustrates the typical failure modes of tested columns under concentric loading. The failure of Columns S-1-4 and S-2-4 was due to the localized buckling of the outer steel tubes, as illustrated in Figure 9. The local buckling was found to occur at the outer tube away from the center of the columns. Similar failure modes of CFDST short columns were observed by Ahmed et al. (2019a). The concrete in the tested columns was crushed at the region where the steel tube buckled. A similar failure mode of concrete was reported by Ahmed et al. (2019a). For Columns S-1-6, S-1-8, S1-10 and S-1-12, which had a larger slenderness ratio than Columns S-1-4 and S-2-4, global buckling of the columns was observed together with the buckling of the outer tubes. For Column S-1-12, buckling of the outer tube occurred at the center of the column. No elephant foot buckling failure was observed for the tested columns. The test results also showed that the utilization of steel clamps prevented the occurrence of elephant foot buckling at the column ends. The failure mode of Columns S-2-8 and S-2-12 were identical to Columns S-1-8 and S-1-12. Failure modes of test specimens. Local buckling of the outer tube of test specimens: (a) short columns and (b) slender columns.

The ultimate compressive loads of CFDST columns
Table 1 summarizes the ultimate loads of the tested columns recorded during the test. It was found that the inner tube provided confinement to the filled concrete that increased the ultimate load of the tested columns. The compressive load of the specimens S-1-4 and S-2-4 was 7% and 6% higher than their nominal load, calculated as
Furthermore, the test compressive strength of confined concrete to concrete cylindrical strength Influences of L/B
0
ratio on the confined compressive strength of concrete. (a) short columns (b) slender columns.
Load-deflection curves of the columns
Figure 11 presents the load-end shortening curves of the tested columns. The residual strength, which was taken as the axial strength at the end of the test (at 30 mm axial shortening) of short Columns S-1-4 and S-2-4 was calculated as 70% and 68% of their ultimate strengths, respectively. The residual strengths of Columns S-1-6, S-1-8, S1-10 and S-1-12 were calculated as 64, 57, 62 and 51%, respectively. Similarly, the residual strengths of Columns S-2-8 and S-2-12 were calculated as 67% and 66%, respectively. This proves that with the increase of the slenderness ratio, the residual strength of the columns decreased. Axial load-end shortening curves of CFDST columns: (a) short columns; (b) slender columns. (a) S-1-6 (b) S-1-8 (c) S-1-10 (d) S-1-12, (e) S-2-8 (f) S-2-12.
The lateral displacements of CFDST slender columns along various heights of the columns at different loading stages were recorded during the tests. From the lateral displacement curves given in Figure 12, it can be seen that with the increase of the axial load, the lateral displacement of the columns increased. However, the increase in the lateral displacement of the columns was significantly higher once the axial load exceeded 75% of the column’s ultimate load. Lateral displacement curves of CFDST slender columns along the column height: (a) S-1-6, (b) S-1-8, (c) S-1-10, (d) S-1-12, (e) S-2-8 and (f) S-2-12.
The axial load-midheight lateral displacement curves (N-δ
m
) of the tested columns are shown in Figure 13. A small drop of the axial load in Column S-1-10 was observed in Figure 13(c), which might be attributed to local buckling in the outer steel skin close to the failure load. Moreover, for Columns S-1-6 and S-2-8, a rapid decrease of the column axial load with the increase of the midspan lateral displacement was observed. This might be because of the excessive local buckling of the outer tube. However, for other tested columns, the N-δ
m
curves can be seen as more flat upon reaching the ultimate load of the columns. Axial load versus mid-height lateral displacement curves of CFDST slender columns: (a) S-1-6, (b) S-1-8, (c) S-1-10, (d) S-1-12, (e) S-2-8 and (f) S-2-12.
Design models of square CFDST slender columns
There are no design specifications available for designing CFDST columns. The applicability of existing design models of CFST columns specified by AISC 360-16 (2016) and Eurocode 4 (2004) for designing square CFDST slender columns is evaluated in this section. The test results obtained from this study are used to validate the design predictions.
Eurocode 4 (2004)
Eurocode 4 (2004) considers the confinement of circular CFST columns and the higher resistance of concrete is accounted for using the concrete coefficient of 1.0 in contrast to other design codes such as AISC 360-16 (2016) and ACI 318-19 (2019), where concrete compressive strength is reduced using a factor, which is usually 0.85. According to Eurocode 4 (2004), the formulae to calculate the ultimate strengths
Circular CFST columns
Rectangular CFST columns
Therefore, the ultimate strength of square CFDST columns can be calculated as:
According to Eurocode 4 (2004), a slenderness reduction factor
In calculating the relative slenderness ratio of CFDST columns
AISC 360-16 (2016)
According to AISC 360-16 (2016), the composite column should be designed based on the category of compact, noncompact or slender sections. A compact section can reach the yield strength, whereas a non-compact section can not reach the yield strength of the steel tube. The normalized slenderness limit according to AISC 360-16 (2016) can be calculated as
C2 in equation (18) was taken as 0.85 for sandwiched concrete and 0.95 for core concrete.
Design model developed by Ahmed et al. (2019b)
Ahmed et al. (2019b) developed design formulae to calculate the ultimate strength of square CFDST slender columns similar to the design guidelines of Eurocode 4 (2004) which applies to a large range of slenderness ratio of the column; however, the accuracy of the model was only validated against the numerical results. The formula to calculate the ultimate strength of the CFDST slender column was suggested as:
In equation (22),
Evaluation of design predictions
Experimental ultimate strengths of square CFDST columns against design predictions.

Comparisons of the design buckling curves with the test results.
Conclusions
This paper presents the test results of square CFDST slender columns subjected to concentric loading. A total of 8 columns were tested, where the test parameters were the column slenderness ratio and the wall thickness of the inner tube. The accuracy of the design guidelines of existing CFST columns specified by various design codes was evaluated in predicting the ultimate strengths of the tested columns by comparing the ultimate strengths. The findings from this study are listed below: (1) The common modes of failure of CFDST columns with a slenderness ratio of less than 8 were the localized buckling of the steel tubes together with the crushing of concrete in the same region. For columns with a higher slenderness ratio, global buckling failure was observed. (2) With the increase of the slenderness ratio, the column ultimate loads were reduced significantly. In addition, decreasing the inner steel wall tube thickness decreased the column ultimate loads. (3) The residual strength of CFDST columns, which was taken as the axial strength at the end of the test (at 30 mm axial shortening), ranged between 51% and 70% of the column’s ultimate strength. The residual strength of the column decreased with the increase in the column slenderness. (4) From the comparisons with the design code predictions, it was found that Eurocode 4 (2004) and AISC 360-16 (2016) significantly underestimated the column ultimate loads. However, the formulae suggested by Ahmed et al. (2019b) provided a better estimation of the column ultimate loads.
This study carried out tests on CFDST slender columns under axial loading. However, tests on CFDST slender columns under axial loading combined with uniaxial bending are also very limited and the accuracy of the N-M interaction curves specified by existing design codes for conventional CFST columns in designing for such a column has not been evaluated yet. Therefore, further tests on such a column under axial loading combined with uniaxial bending can be undertaken in the future to compare the N-M interaction curves.
Footnotes
Declaration of Conflicting Interests
The author(s) declared no potential conflicts of interest with respect to the research, authorship, and/or publication of this article.
Funding
The author(s) received no financial support for the research, authorship, and/or publication of this article.
